Item | Specification |
Input and Output Characteristics | Rated Input Voltage | 200V voltage level: single/three-phase 220VAC |
400V voltage level: three-phase 380VAC voltage, continuous fluctuation ±10%, brief fluctuation -15%to+10% |
Rated Input Frequency | 50Hz/60Hz±5% |
Output Voltage | 3 phases: 0 to rated input voltage, error less than ±3% |
Output Frequency | 0.00~500.00Hz, unit 0.01Hz |
Overload Capacity | 150% 1 minute; 180% 10 seconds; 200%0.5 seconds |
Operation Control Characteristics | Control Method | V/f control PG-free vector control (SVC) |
Speed Range | 1:100 (V/f) 1:200 (SVC) |
Speed Control Accuracy | ±0.5% (V/f control) ±0.2% (SVC) |
Speed Fluctuations | ±0.3% (SVC) |
Torque Response | <10ms (SVC) |
Starting Torque | 0.5Hz: 180% (V/f, SVC) 0.25Hz: 180% (SVC) |
Basic Function | V/F Curve | Three ways: linear; multi-point; Nth order V/F curve |
V/F Separation | 2 ways: full separation, semi-separation |
Acceleration and Deceleration Curves | Straight line or S curve acceleration and deceleration mode; four acceleration and deceleration times; acceleration and deceleration time range 0.0~60000s |
DC Brake | DC braking frequency: 0.00Hz~maximumfrequency, braking time: 0.0s~30.0s, braking action current value: 0.0%~100.0% |
JOG Control | JOG frequency range: 0.00Hz~50.00Hz; JOG acceleration and deceleration time 0.0s~60000s |
Simple PLC, multi-segment Operation | Up to 16-speed operation via built-in PLC or control terminal |
Built-in PID | Easy to implement closed-loop control systemfor process control |
| When the grid voltage changes, it can automatically maintain the output voltage constant |
Automatic limitation of current and voltage during operation to prevent frequent over-current and over-voltage tripping |
Minimize overcurrent faults and protect products from normal operation |
Torque Limiting and Control | Automatic torque limitation during operation to prevent frequent overcurrent tripping |
Input Terminals | Six switching input terminals, including X6 for high-speed pulse input. Support active open collector NPN, PNP and dry contact input mode, two analog input terminals, one for voltage and current input optional, one for voltage input |
Output Terminals | A high-speed pulse output terminal, 0 ~ 50kHz square wave signal output, can realize the set frequency, output frequency and other physical quantity output, a switch output terminal, a set of relay output terminal |
One analog output terminal, voltage and current output can be selected to realize the output of physical quantities such as set frequency and output frequency |
Features | Various main and auxiliary feed and switch, speed search, multiple acceleration and deceleration curves selection, holding brake control, up to 16-segment speed operation (two-segment speed support flexible frequency feed), swing frequency control operation, fixed length control, counting function, over-excitation braking, over-voltage stall, under-voltage stall, power failure restart, jump frequency, frequency binding, four-segment acceleration and deceleration time free switching, motor temperature protection, flexible fan control, process PID control, simple PLC, sag control, parameter recognition, weak magnetic control, high precision torque limiting, V/f separation control |
Protection Function | Power-on motor short-circuit detection, over-current protection, overvoltage protection, undervoltage protection, overheat protection, overload protection, etc |
Environment | Place of use | Indoor, not exposed to direct sunlight, no dust, corrosive gases, flammable gases, oil mist, water vapor, dripping water or salt, etc. |
Altitude | The rated output current will be derated by 1%for every 100 meters of elevation above 1000 meters. |
Ambient Temperature | -10℃~40℃, 40℃~50℃between the derating use, rise1℃, the rated output current is reduced by 1% |
Humidity | 5~95%, no condensation allowed |
Vibration | Less than 5.9 m/s 2 (0.6g) |
Storage Temperature | -20℃~+60℃ |
Other | Installation Method | Wall-mounted |
Protection Level | IP20 |
Cooling Method | Forced air cooling |